Fire Hazard Properties

Report FAR 4659 lists the Group Number and Average Specific Extinction Area of all Knauf wall and ceiling linings in accordance with AS 5637.1 : 2015.

AS 5637.1 determines what type of fire test the product must be subjected to; a small scale ‘cone calorimeter test’ to AS/NZS 3837 or a large scale corner/room test to ISO 9705.  The output of these tests are often referred to as ‘product fire test reports’.

Download here

The BCA (Building Code of Australia) regulates the fire hazard properties of lining materials in Class 2 to 9 buildings according to Specification C1.10.  Wall and ceiling linings must have a low enough group number for use in certain areas depending on the Class of building. The group number indicates how quickly wall and ceiling linings spread fire with Group 1 products the slowest and Group 4 the fastest. Wall and ceiling linings in some buildings must also have a Smoke Growth Rate Index not more than 100, or an Average Specific Extinction Area less than 250 m2/kg.

Most of the tested Knauf wall and ceiling linings are Group 1 except plasterboard ceiling tiles covered with plastic (vinyl or polyolefin).  

All Knauf wall and ceiling linings tested had an Average Specific Extinction Area of <250 m2/kg as required by BCA Specification C1.10.  

ProductsGroup No.
MastaShield1
SpanShield1
WaterShield1
FireShield1
MultiShield1
SoundShield1
CurveShield1
TruRock1
OPAL1
Knauf Shaftliner1
Permarock1
Designpanel1
Stratopanel1
Contrapanel1
SpanGrid - Paper-faced1
SpanGrid - Vinyl-faced2
SpanGrid - Polyolefin2
Plaza1